Size the exact minimum wire gauge in AWG or mm² and check real voltage drop (%) for EV chargers, solar runs, home subpanels, and DC circuits — running 100% locally in your browser.
Voltage Drop Formula & Wire Resistance Math
Built on fundamental electrical voltage drop physics and aligned with European REBT wiring standards (for metric runs):
Single-Phase / DC: V_drop = (2 × L_m × I × ρ) / Area_mm²
Three-Phase AC: V_drop = (√3 × L_m × I × ρ) / Area_mm²
AWG vs Metric mm² Reference Chart (Copper)
| American Wire Gauge (AWG) | Cross-Section (mm²) | Typical Breaker Rating | Common Real-World Circuits |
|---|---|---|---|
| 14 AWG | 2.08 mm² (~2.5 mm²) | 15 A | 120V lighting & light outlets |
| 12 AWG | 3.31 mm² (~4.0 mm²) | 20 A | Kitchen/bathroom 20A circuits |
| 10 AWG | 5.26 mm² (~6.0 mm²) | 30 A | Water heaters, dryers, short 240V EV |
| 8 AWG | 8.37 mm² (~10.0 mm²) | 40 A | Long 32A–40A EV wallboxes, HVAC condensers |
| 6 AWG | 13.30 mm² (~16.0 mm²) | 50–60 A | 48A hardwired EV chargers, garage subpanels |
Frequently Asked Questions
Why do 48V solar battery cables need huge thickness compared to 240V AC lines?
Because current equals Watts / Volts. Carrying 2,400 W at 48 V pulls 50 Amps — five times higher current than 240 V — multiplying I²R resistive heat loss by 25× for the same wire gauge.
Is passing a voltage drop check enough for electrical code compliance?
No: conductor ampacity (temperature insulation rating such as 75°C THHN, conduit fill, and ambient derating) must always satisfy local code alongside voltage drop limits.